Vivarium Air Change Calculator

Compute air changes per hour from CFM and room volume, check NIH Guide compliance, assess heat load balance, and evaluate pressurization for vivarium rooms.

Vivarium OperationsHVAC ComplianceClient-Side

Try it out

Load example vivarium air change calculator data to see the full workflow

Room Volume

Airflow

Heat Load & Temperature

Warnings
  • Effective ACH (0.0) is below NIH Guide minimum of 10.
  • Room heat load exceeds air cooling capacity — risk of temperature exceedance.

Results

Effective ACH
0
below-minimum
Volume
3,000
ft³
Pressure
0
CFM (neutral)
Heat Balance
Over
800 BTU/hr
Supply ACH0
Exhaust ACH0
NIH StatusACH of 0.0 is below NIH Guide minimum of 10. Increase supply airflow.
Heat Removal Capacity0 BTU/hr
Heat BalanceHeat load (800 BTU/hr) exceeds removal capacity (0 BTU/hr). Room may overheat.
  • Verifying NIH Guide compliance for animal room ventilation
  • Sizing HVAC for a new vivarium build or renovation
  • Assessing whether a room can handle additional cages
  • Checking heat balance before increasing animal density
  • Evaluating VAV system min/max settings

Don't use for

  • Full HVAC design (requires engineering analysis)
  • Humidity or particulate calculations (outside scope)
  • Biosafety cabinet airflow validation

Vivarium HVAC and the NIH Guide

The NIH Guide for the Care and Use of Laboratory Animals (8th edition) establishes environmental standards for animal housing. Section on Macroenvironment specifies:

  • Temperature: 68–79°F (20–26°C) for most rodents, with ±2°F stability
  • Relative humidity: 30–70%
  • Air changes: 10–15 ACH is the long-standing recommendation
  • Ventilation strategy: 100% outside air is preferred; recirculation requires HEPA filtration

The 10–15 ACH range balances three competing needs: 1. Gas dilution: Ammonia from urine must stay below 25 ppm (OSHA PEL) 2. Heat removal: A room of 200+ mouse cages generates significant sensible heat 3. Energy cost: Each CFM of conditioned air costs $2–4/year in energy

Modern facilities increasingly use demand-controlled ventilation (DCV) that modulates airflow based on real-time ammonia or CO₂ sensors, allowing ACH to drop to 5–8 during unoccupied periods while ramping up during cage changes. AAALAC accepts DCV systems that maintain adequate air quality as documented by environmental monitoring.

Frequently Asked Questions