-86℃ Freezer (Inverter Type)
From $5,799.00
Research data · Cold storage
On EPA's ENERGY STAR list, the median ultra-low temperature freezer uses 8.72 kWh a day at -80 °C and 5.98 kWh at -70 °C.
Model by model, -70 °C in place of -80 °C saves a median of 30% of a freezer's daily use. The saving runs from 9.5% to 40.1%.
Daily energy use of each ultra-low temperature freezer on EPA's list, at both test temperatures
Each pair of dots is one model, and the line between them is its saving at -70 °C (median 30%).
| Volume (liters) | Volume (cubic feet) | kWh a day at -80 °C | kWh a day at -70 °C | Saving |
|---|---|---|---|---|
| 421 | 14.87 | 8.01 | 5.86 | 26.8% |
| 421 | 14.87 | 8.01 | 5.86 | 26.8% |
| 524 | 18.5 | 5.43 | 4.33 | 20.3% |
| 524 | 18.5 | 5.43 | 4.33 | 20.3% |
| 527 | 18.6 | 6.84 | 5.44 | 20.5% |
| 530 | 18.7 | 7.79 | 6.27 | 19.5% |
| 530 | 18.7 | 8.44 | 5.94 | 29.6% |
| 530 | 18.7 | 9.58 | 6.28 | 34.4% |
| 531 | 18.75 | 7.14 | 5.56 | 22.1% |
| 532 | 18.78 | 7.56 | 6.20 | 18% |
| 547 | 19.31 | 8.71 | 5.78 | 33.6% |
| 547 | 19.31 | 8.71 | 5.78 | 33.6% |
| 549 | 19.39 | 8.44 | 5.67 | 32.8% |
| 549 | 19.39 | 8.44 | 5.67 | 32.8% |
| 549 | 19.39 | 8.44 | 5.67 | 32.8% |
| 564 | 19.93 | 8.37 | 5.49 | 34.4% |
| 564 | 19.93 | 8.37 | 5.49 | 34.4% |
| 581 | 20.52 | 4.93 | 3.43 | 30.4% |
| 581 | 20.52 | 4.93 | 3.43 | 30.4% |
| 581 | 20.52 | 6.63 | 4.72 | 28.8% |
| 581 | 20.52 | 6.63 | 4.72 | 28.8% |
| 581 | 20.52 | 8.27 | 5.42 | 34.5% |
| 581 | 20.52 | 8.27 | 5.42 | 34.5% |
| 581 | 20.52 | 8.27 | 5.42 | 34.5% |
| 682 | 24.09 | 8.72 | 5.90 | 32.3% |
| 682 | 24.09 | 8.72 | 5.90 | 32.3% |
| 682 | 24.09 | 8.72 | 5.90 | 32.3% |
| 682 | 24.09 | 9.06 | 5.98 | 34% |
| 682 | 24.09 | 9.06 | 5.98 | 34% |
| 702 | 24.79 | 8.32 | 5.24 | 37% |
| 702 | 24.79 | 8.32 | 5.24 | 37% |
| 719 | 25.4 | 4.71 | 3.66 | 22.3% |
| 719 | 25.4 | 4.71 | 3.66 | 22.3% |
| 720 | 25.42 | 9.66 | 6.28 | 35% |
| 720 | 25.42 | 9.66 | 6.28 | 35% |
| 720 | 25.42 | 9.66 | 6.28 | 35% |
| 720 | 25.42 | 10.29 | 7.28 | 29.3% |
| 720 | 25.42 | 10.29 | 7.28 | 29.3% |
| 720 | 25.42 | 10.29 | 7.28 | 29.3% |
| 729 | 25.74 | 9.00 | 6.72 | 25.3% |
| 733 | 25.9 | 6.01 | 4.89 | 18.6% |
| 733 | 25.9 | 6.01 | 4.89 | 18.6% |
| 733 | 25.9 | 8.57 | 7.00 | 18.3% |
| 734 | 25.93 | 8.82 | 6.34 | 28.1% |
| 736 | 26 | 8.35 | 6.51 | 22% |
| 736 | 26 | 8.35 | 6.51 | 22% |
| 751 | 26.53 | 10.16 | 7.88 | 22.4% |
| 779 | 27.5 | 9.39 | 7.40 | 21.2% |
| 779 | 27.5 | 9.95 | 7.27 | 26.9% |
| 791 | 27.92 | 7.36 | 6.07 | 17.5% |
| 794 | 28.04 | 6.70 | 5.58 | 16.7% |
| 815 | 28.79 | 9.43 | 6.16 | 34.7% |
| 815 | 28.79 | 9.43 | 6.16 | 34.7% |
| 815 | 28.79 | 9.43 | 6.16 | 34.7% |
| 815 | 28.79 | 10.44 | 8.02 | 23.2% |
| 816 | 28.82 | 8.78 | 5.96 | 32.1% |
| 816 | 28.82 | 8.78 | 5.96 | 32.1% |
| 816 | 28.82 | 8.78 | 5.96 | 32.1% |
| 825 | 29.14 | 5.98 | 4.43 | 25.9% |
| 825 | 29.14 | 5.98 | 4.43 | 25.9% |
| 825 | 29.14 | 11.82 | 7.74 | 34.5% |
| 825 | 29.14 | 11.82 | 7.74 | 34.5% |
| 829 | 29.27 | 9.57 | 6.86 | 28.3% |
| 829 | 29.27 | 9.57 | 6.86 | 28.3% |
| 829 | 29.27 | 9.57 | 6.86 | 28.3% |
| 839 | 29.62 | 10.54 | 6.31 | 40.1% |
| 839 | 29.62 | 10.54 | 6.31 | 40.1% |
| 852 | 30.1 | 10.13 | 7.58 | 25.2% |
| 861 | 30.4 | 10.62 | 8.96 | 15.6% |
| 937 | 33.09 | 10.85 | 9.82 | 9.5% |
| 950 | 33.56 | 9.67 | 6.62 | 31.5% |
| 950 | 33.56 | 9.67 | 6.62 | 31.5% |
| 959 | 33.85 | 9.30 | 6.17 | 33.7% |
| 959 | 33.85 | 9.30 | 6.17 | 33.7% |
| 960 | 33.9 | 5.60 | 4.30 | 23.2% |
| 960 | 33.9 | 5.60 | 4.30 | 23.2% |
| 960 | 33.9 | 13.19 | 9.07 | 31.2% |
| 960 | 33.9 | 13.19 | 9.07 | 31.2% |
Across the 78 freezers on the list, the median daily use at -80 °C is 8.72 kWh, or 3,183 kWh a year. At -80 °C, daily use runs from 4.71 kWh to 13.19 kWh. Every model uses less at -70 °C. Larger freezers tend to use more. At -80 °C, freezers of 729 liters (25.74 cubic feet) and up, the larger half of the list, use a median of 9.43 kWh a day, and the smaller half uses 8.37 kWh.
At the 2025 U.S. average commercial price of 13.37 cents a kWh, the median daily use costs $426 a year at -80 °C and $292 at -70 °C. State prices run from 7.36 cents a kWh in North Dakota to 36.31 cents in Hawaii.
| Freezer | At -80 °C | At -70 °C |
|---|---|---|
| Median use | $426 | $292 |
| Lowest use | $230 | $167 |
| Highest use | $644 | $479 |
Each column takes the median, lowest and highest use at its own setting, so a row's two figures can come from different models.
To cost your own freezer, enter its daily use, your electricity price and your room's temperature in the operating cost calculator.
The list also holds 1,084 lab refrigerators and freezers that are not ultra-low temperature freezers. Most of them are in EPA's high performance class. The median high performance refrigerator uses 1.41 kWh a day, and the median high performance freezer 2.08 kWh. At close median volumes of 523 and 497 liters, high performance refrigerators with glass doors use more than those with solid doors, a median of 1.47 kWh a day against 1.15 kWh.
Daily energy use against volume, for the other refrigerators and freezers on EPA's list
Each dot is one model.
| Type | Doors | Models | Share of the list | Median volume (liters) | Median kWh a day |
|---|---|---|---|---|---|
| High performance refrigerators | Glass | 720 | 62% | 523 | 1.47 |
| High performance refrigerators | Solid | 232 | 20% | 497 | 1.15 |
| High performance freezers | Solid | 113 | 10% | 476 | 2.08 |
| General purpose refrigerators | Solid | 10 | 1% | 790 | 1.48 |
| General purpose freezers | Glass | 1 | under 1% | 1,313 | 7.39 |
| General purpose freezers | Solid | 8 | 1% | 229 | 1.42 |
Of the list's 1,162 models, 653 use propane (R-290), the most common refrigerant, and 506 use isobutane (R-600a). Ethane, R-170, is used only in ultra-low temperature freezers: 67 of the 78 use it. Every ultra-low temperature freezer on the list names two or more refrigerants, so the shares below add up to more than 100%. Only 1 model on the list uses R-404A, a blend with a global warming potential of 3,920. EPA gives propane 3 and ethane 5.5.
A freezer at the median use gives off 363 watts at -80 °C, or 1,240 BTU an hour, and 249 watts at -70 °C, or 850 BTU an hour. That counts every kWh it uses as heat given off into the room, as the freezer room heat load calculator does.
To add up the heat of every unit in a room, open the freezer room heat load calculator.
The energy figures above come from EPA's list, not from these units. Each card shows the unit's name and price from our catalog.